5. Press «UP».
The check box is activated.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.2.3.1 pA/pB Clock
Menu
Reset: ☒
Active line, delete existing clock program
·········
01 n.a. 00:00 pA
First switching point deleted
02 n.a. 00:00 pA
Second switching point deleted
03 n.a. 00:00 pA
Third switching point deleted
04 n.a. 00:00 pA
Fourth switching point deleted
6. Press «Enter» to accept the setting.
You have deleted the existing clock program.
All switching points are reset to
pA
.
The
Reset
check box is deactivated automatically.
7. Press the «DOWN» key repeatedly until the switching point 01 is displayed as the active line.
8. Press «Enter» to switch into setting mode.
The
Weekdays
column flashes.
9. Press «UP» repeatedly until Mon-Fri appears.
10. Press «Enter» to accept the setting.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.2.3.1 pA/pB Clock
Menu
Reset: ☐
·········
01 Mon-Fri 00:00 pB
Active line, First switching point, set weekdays
02 Mon-Fri 00:00 pB
Weekday Second switching point
03 n.a. 00:00 pB
04 n.a. 00:00 pB
11. Enter the weekdays for the second switching point in the same manner.
Result The weekdays for the first two switching points are set.
Set the time for the first two switching points
1. Press the «UP» key repeatedly until the switching point 01 is displayed as the active line.
2. Press the «Right» key once.
3. Press «Enter» to switch into setting mode.
The column time, display for hours,
00 : 00
in the active line flashes.
4. Use «UP» to specify the settings for the hours.
5. Press the «Right» key once.
The column time, display for minutes,
00 : 00
in the active line flashes.
6. Use «UP» to specify the settings for the minutes.
7 Initial Start-up
7.9 Configuring the machine for master control
118
Service manual Controller