Setting a clock program Setting the timer
1. Select the
< Configuration ➙ Pressure
control ➙ Load control >
menu.
2. Press «DOWN» five times.
3. Press «Enter» to open the
< pA/pB Clock >
menu.
4. Press «Enter» to switch into the setting
mode for the first switching point.
5. Use «UP» or «DOWN» to set the week‐
days.
6. Press «Enter» to accept the setting.
7. Press «Right» to set the time.
8. Press «Enter» to switch into the time setting
mode.
9. Use «UP» or «DOWN» to set the hours.
10. Press «Right» to set the minutes.
11. Use «UP» or «DOWN» to set the minutes.
12. Press «Enter» to accept the time settings.
13. Press «Right» to set the system setpoint
pressure.
14. Press «Enter» to switch into the setting
mode for system setpoint pressure pA or
pB.
15. Press «UP» or «DOWN» to set the system
setpoint pressure.
16. Press «Enter» to accept the setting.
1. Select the
< Configuration ➙ Pressure
control ➙ Load control >
menu.
2. Press «DOWN» eight times to define the
timer period for system setpoint pressure pA
and pB.
3. Press «Enter» to switch into the setting
mode for the system setpoint pressure pA.
4. Use «UP» or «DOWN» to set the timer peri‐
od for the system setpoint pressure pA.
5. Press «Enter» to accept the setting.
6. Press the «Right» key.
7. Press «Enter» to switch into the setting
mode for system setpoint pressure pB.
8. Use «UP» or «DOWN» to set the timer peri‐
od for the system setpoint pressure pB.
9. Press «Enter» to accept the setting.
10. Press «DOWN» once.
11. Press «Enter» to switch into the setting
mode for the first start of system setpoint
pressure pA or pB.
12. Use «UP» or «DOWN» to set the first start
of system setpoint pressure pA.
13. Press «Enter» to accept the setting.
14. Press «Right» to set the starting time.
15. Press «Enter» to switch into the setting
mode for the starting time.
16. Use «UP» or «DOWN» to set the hours.
17. Press «Right» to set the minutes.
18. Use «UP» or «DOWN» to set the minutes.
19. Press «Enter» to accept the settings for the
starting time.
IP configuration
If the controllers of both machines are linked directly, they must have different IP addresses.
Example:
■ Controller machine 1 (Master mode): 169.254.100.101
■ Controller machine 2 (Slave mode): 169.254.100.102
1. Select
< Communication ➙ Ethernet ➙ IP configuration >
.
2. Enter IP address for the slave.
3. Select
< Communication ➙ Ethernet ➙ Connections ➙ SIGMA CONTROL 2 >
.
4. Press «DOWN» twice.
5. Press «Enter» to switch into setting mode.
6. Use «UP» to et the controller of machine 1 to “Master”.
7 Initial Start-up
7.9 Configuring the machine for master control
102
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3 9_9450 03USE