EasyManua.ls Logo

KAESER ESD.2C - Configuring for Master Control with Local;Load Remote Contact; Making the Electrical Connection

KAESER ESD.2C
413 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4. Press «Enter» to accept the setting.
The «Remote control» key is activated and can be used.
5. Press the «Remote control» key to enable remote mode.
7.9.6 Configuring for master control with local/LOAD remote contact
Overview
Making the electrical connection
Setting the local/LOAD remote contact operating mode and assign the input.
Configuring the local operating mode, if necessary.
Activating the «Remote control» key
Configuring master control as described below.
7.9.6.1 Making the electrical connection
Use the input “Controller On (DOR 1.03) for the "alarm machine X" message to prevent line
breaks!
Wire the "motor running” and "Controller on” (DOR 1.03) messages from the compressor
to the MVS 8000 controller.
Contact A open: SIGMA CONTROL 2 controls with system setpoint pressurepB
Contact A closed: SIGMA CONTROL 2 controls using a remote contact input.
DI 1.13: LOAD/IDLE external
DI 1.09: LOAD control – switchover local/LOAD remote contact.
Fig. 33 Wiring diagram for local/LOAD remote contact:
A Changeover between automatic and manual modes
B LOAD/IDLE contact
Make the electrical connection according to the diagram.
7.9.6.2 Setting the local/LOAD remote contact operating mode and assigning the input
Precondition Access level 2 is activated.
The
< Configuration ➙ Pressure control ➙ Load control >
menu is selected.
7 Initial Start-up
7.9 Configuring the machine for master control
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
107

Table of Contents

Related product manuals