3. Press «Enter» to accept the setting.
The offset is reset to
32 °F
.
The test mode is deactivated and the test is completed.
4. Press «Escape» repeatedly to return to the main menu.
Resetting
SIGMA CONTROL 2 will display the highest measured value if the test for switching off at overtem‐
perature is aborted.
Activate the check box for reset in order to reset the stored value.
Activate the check box.
8 Operation
8.11 Checking the temperature sensor and overheating shutdown function
156
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3 9_9450 03USE