Chapter 11 Datalog Function
11.2 Performance Specifications
Function
Configuration
regular / trigger / event
Data Type
BIT, BYTE, WORD, DWORD, LWORD, SINT, INT, DINT, LINT
USINT, UINT, UDINT, ULINT, REAL, LREAL, STRING
Decimal, Hexadecimal, Exponent, character string
Regular Save
Main-task Cycle, Designation Cycle, Designation Time
File
Conversion
Designate with File Size 10 ~ 16,384KB
Designate with No. of Save Lines 1,000~50,000
Maximum
256 per folder
Trigger Save
Single Condition
Bit: elevation/descent
Word: small, big, same, different, big or same, small or same
Up to 69,905 data per group
Files
Conversion
Designate with File Size 10 ~ 16,384KB
Designate with No. of Save Lines 1,000~50,000
256 per folder
Event Save
Single Condition
Bit: ON, OFF, elevation, descent, transfer
Word: small, big, same, different, big or same, small or same
Files
Conversion
Conversion
Designate with File Size 10 ~ 16,384KB
Designate with No. of Save Lines 1,000~50,000
256 per folder
Formatting
Function
SD memory
Maximum Capacity
Up to 32GB
( Only 8GB can be available for above 8GB memory size)
Memory Type
Micro SD, SDHC
(Recommended manufacturer: SanDisk, Transcend)
Note
SanDisk, Transcend SD memories are recommended for internal datalog. Use of SD memory from other
manufacturer may result in unexpected run. Please choose your SD memory card with caution.