Chapter 11 Datalog Function
11.5.1 Trigger Condition
Trigger Save function runs under Single Condition, Multiple Condition. The setting item for single/multiple conditions
are as follows. Multiple Condition runs by connecting Single Condition using AND, OR. Up to 4 Single Conditions can
be set to form a condition. When the Trigger Condition occurs and data saving initiates, T character string is inserted
into the first data string to indicate the trigger starting point.
(1) Single Condition
Single Condition runs under [BIT Condition], [WORD Condition].
(a) BIT Condition
BIT condition checks the set device BIT value, and collects data by detecting trigger when the value is either
[elevation] or [descent].
(b) WORD Condition
Word Condition compares the set device with the input value, and converts them into TRUE or FALSE. If the set
device value satisfies the input condition, data are collected when the value is either [elevation] or [descent].
Ex) If set value is <50, elevation condition