Chapter 13 Built-in Analog Function
(2) Output performance specification
Performance specification
Analog
output
Range
0 to 5 V DC
0 to 10 V DC
-10 to 10 V DC
(Load resistance: 1 ㏀ or more)
Output ranges are set in user program or I/O parameter per each channel.
Digital
range
Precise value
1,000 to 5,000 (1 to 5 V)
0 to 5,000 (0 to 5 V)
0 to 10,000 (0 to 10 V)
-10,000 to 10,000 (±10 V)
Max. resolution
㎷
0.3125 ㎷ (0 to 5 V)
0.625 ㎷ (0 to 10 V)
1.250 ㎷ (±10 V)
Accuracy
±0.2% or less (When ambient temperature is 25±5℃)
±0.3% or less (When ambient temperature is 0 to 55℃)
㎳
Additional function
• Setting of channel output status
- Select one among previous, minimum, average, maximum value
• Setting of interpolation method
- Linear interpolation, S-type interpolation
(3) Common performance specification
Performance specification
Insulation method
Photo-coupler and trans insulation between the input/output terminal and motion
controller power (no insulation between channels)
Fixed point assignment: 64 points