Chapter 13 Built-in Analog Function
13.5.5 Hold Last Value Function
When input signal exceeds the effective range, last input value is held. This function can be set for each channel by
I/O parameter setting or user program.
(1) Used input range
In the channels that allow the hold last value function, the actual ranges provided within each digital
conversion value are shown. For example, in case of operating output data type of unsigned value, original
digital output value is shown from -192 to 16,191. However, if this function is allowed, it will be shown from 0 to
16,000. It is recommended that the function should be setting when the input value is in the actual range.
(a) Digital output value depending on input range (unsigned value, signed value, percentile value)
(2) Reference
(b) Digital output value depending on input range (Precise value)
4 to 20 ㎃
0 to 20 ㎃
1 to 5 V
0 to 5 V
0 to 10 V
-10 to 10 V
(2) Operation
When operating with 4 to 20 mA while being enabled this function, output value for input value change of the
moment is as follows (Output data type: In case of 0 to 16,000).
Remarks -
- -
-