Chapter 3 Operation Order and Installation
The load
doesn’t turn off
Leakage current by surge absorbing circuit,
which is connected to output element in parallel.
Connect C and R across the load, which are of
registers of tens KΩ. When the wiring distance from
the output module to the load is long, there may be a
leakage current due to the line capacity.
When the load
is C-R type
timer, time
constant
fluctuates
Leakage current by surge absorbing circuit,
which is connected to output element in parallel.
Drive the relay using a contact and drive the C-R
type timer using the since contact.
Use other timer than the CR contact some timers
have half-ware rectified internal circuits therefore, be
cautious.
The load does
not turn off
Sneak current due to the use of two different
power supplies.
E1<E2, sneaks. E1 is off (E2 is on), sneaks.
Use only one power supply.
Connect a sneak current prevention diode.
If the load is the relay, etc, connect a counter-
electromotive voltage absorbing code as shown by
the dot line.