Startup Procedure and Test Run
4
4.9 Auto-Tuning
SIEPCYEUOQ2V01A Q2V Technical Manual 129
Precautions before Stationary Auto-Tuning
Make sure that the motor magnetic brake is not open.
Make sure that external force from the machine will not cause the motor to rotate.
WARNING! Electrical Shock Hazard. During Auto-Tuning, the motor will receive high voltage when the motor is stopped. Do not
touch the motor until Auto-Tuning is complete. If you touch a motor that is energized, it can cause serious injury or death.
Automatically Set E2-02 [Mot Rated Slip] and E2-03 [Mot No-Load Current]
If T1-12 = 1 [Test Mode Selection = Yes] when selecting Stationary Auto-Tuning, the drive will automatically set
motor parameters E2-02 [Mot Rated Slip] and E2-03 [Mot No-Load Current] after Auto-Tuning is complete when
you use the motor for the first time in Drive Mode.
After Stationary Auto-Tuning is complete, use this procedure to do the operation in test mode:
1. Check the E2-02 and E2-03 values on the Modified Parameters/Fault Log screen or the Parameters screen.
2. Operate the motor in Drive Mode with these conditions:
Make sure that you connect all wiring between the drive and motor
Make sure that a mechanical brake on the motor shaft is not locked
The maximum motor load must be 30% of the rated load.
Keep a constant speed of 30% of E1-06 [Base Frequency] (default value = maximum frequency) or more
for 1 second or longer.
3. After the motor stops, examine the values of E2-02 and E2-03 again in the Verify Menu or Parameter Setting
Mode.
4. Make sure that the input data is correct.
When the settings in E2-02 and E2-03 are different than in step 1, the drive set the values automatically.
Precautions before Stationary Auto-Tuning for Line-to-Line Resistance and Stator
Resistance Auto-Tuning
In V/f control, when the motor cable is 50 meters (164 feet) or longer, do Stationary Auto-Tuning for Line-to-Line
Resistance.
WARNING! Electrical Shock Hazard. During Auto-Tuning, the motor will receive high voltage when the motor is stopped. Do not
touch the motor until Auto-Tuning is complete. If you touch a motor that is energized, it can cause serious injury or death.
Precautions before Using Deceleration Rate Tuning and KEB Tuning
Before Deceleration Rate Tuning or KEB Tuning, check these items:
Do not do Deceleration Rate Tuning if you use a braking resistor unit or a regenerative converter.
Do Deceleration Rate Tuning and KEB Tuning with the load attached to the motor.
Do not do Deceleration Rate Tuning or KEB Tuning for these applications:
In Deceleration Rate Tuning and KEB Tuning, the drive will automatically rotate the motor forward and
accelerate and decelerate the motor again and again.
On a machine that does not let the motor rotate forward
In applications with a small range of operation (trolleys and other such applications that can only move
linearly)
In elevator applications
Applications where sudden acceleration and sudden deceleration are not applicable.
To do KEB Tuning with the external main circuit capacitors connected to the drive, set L3-26 [DC Bus
Capacitors Extension] then do KEB Tuning.
Do not do KEB Tuning or Deceleration Rate Tuning if the drive is set to use H1-xx = 61 [MFDI Function
Select = Motor 2 Select]. Failure to obey can cause an ov [Overvoltage] fault.