Specifications
10
10.2 Drive Duty Modes
SIEPCYEUOQ2V01A Q2V Technical Manual 291
10.2 Drive Duty Modes
The drive has two duty modes from which to select for the application: Heavy Duty (HD) and Normal Duty (ND).
Table 10.1 Drive Duty Modes
Duty Rating
C6-01
Setting
Application Default Carrier Frequency
Overload Tolerance (oL2
[Drive Overload])
Heavy Duty Rating
(HD)
0
Extruder
Conveyor
Cranes and hoists
Constant torque or high overload capacity
Determined by o2-04, A1-02
150% of the rated output current for
60 seconds The permitted
frequency of overload is once every
10 minutes.
Normal Duty Rating
(ND)
1
Fan
Pump
Blower
Variable speed control
Determined by o2-04, A1-02
110% of the rated output current for
60 seconds The permitted
frequency of overload is once every
10 minutes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2V Series and is the answer not in the manual?

Omron Q2V Series Specifications

General IconGeneral
BrandOmron
ModelQ2V Series
CategoryInverter
LanguageEnglish

Related product manuals