EasyManua.ls Logo

Omron Q2V Series - L7: Torque Limit; L8: Drive Protection

Omron Q2V Series
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.10 L: PROTECTION
372 SIEPCYEUOQ2V01A Q2V Technical Manual
L7: TORQUE LIMIT
No.
(Hex.)
Name Description
Default
(Range)
Ref.
L7-01
(04A7)
RUN
FW Torque Limit
Sets the torque limit value for forward motoring as a percentage, where motor rated
torque is the 100% value.
200%
(0 - 300%)
666
L7-02
(04A8)
RUN
RV Torque Limit
Sets the torque limit value for reversed motoring as a percentage, where motor rated
torque is the 100% value.
200%
(0 - 300%)
666
L7-03
(04A9)
RUN
FW Reg. TrqLimit
Sets the torque limit value for forward regenerative conditions as a percentage of the
motor rated torque.
200%
(0 - 300%)
667
L7-04
(04AA)
RUN
RV Reg. TrqLimit
Sets the torque limit value for reversed regenerative conditions as a percentage of the
motor rated torque.
200%
(0 - 300%)
667
L7-06
(04AC)
TrqLimit Integral Time
Sets the integral time constant for the torque limit function.
200 ms
(5 - 10000 ms)
667
L7-07
(04C9)
TrqLimit@Acc/Decel
Sets the torque limit function during acceleration and deceleration.
1 : P-ctrl@Ac/Dec
2 : I-ctrl@Ac/Dec
1
(1, 2)
667
L7-16
(044D)
TrqLimit@Start
Assigns a time filter to allow the torque limit to build at start.
0 : Disabled
1 : Enabled
1
(0, 1)
668
L8: DRIVE PROTECTION
No.
(Hex.)
Name Description
Default
(Range)
Ref.
L8-01
(04AD)
3%ERF DBR Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series
braking resistor (3% ED) installed on the heatsink.
0 : Disabled
1 : Enabled
0
(0, 1)
668
L8-02
(04AE)
Overheat Alm Level
Sets the oH detection level in temperature.
Determined by o2-04,
C6-01
(50 - 150 °C)
668
L8-03
(04AF)
Overheat Pre-Alarm
Selection
Sets the operation of drives when an oH alarm is detected.
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
4 : Run@L8-19 Rate
3
(0 - 4)
668
L8-05
(04B1)
In PhaseLoss Selection
Sets the function to enable and disable input phase loss detection.
0 : Disabled
1 : Enabled
1
(0, 1)
669
L8-07
(04B3)
Out PhaseLoss Selection
Sets the function to enable and disable output phase loss detection. The drive starts
output phase loss detection when the output current decreases to less than 5% of the
drive rated current.
Note:
The drive can incorrectly start output phase loss detection in these conditions:
The motor rated current is very small compared to the drive rating.
The drive is operating a PM motor with a small load.
0 : Disabled
1 : 1PH Loss Det
2 : 2/3PH Loss Det
0
(0 - 2)
669
L8-09
(04B5)
Ground Fault Selection
Sets the function to enable and disable ground fault protection.
0 : Disabled
1 : Enabled
Determined by o2-04
(0, 1)
670

Table of Contents

Related product manuals