EasyManua.ls Logo

Omron Q2V Series - Control I;O Connections; Set Sinking Mode;Sourcing Mode; Pulse Train Output

Omron Q2V Series
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation
3
3.6 Control I/O Connections
SIEPCYEUOQ2V01A Q2V Technical Manual 81
3.6 Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
MFDI (terminals DI1 to DI7)
Pulse train output (terminal PO)
MFAI (terminal AI2)
MFAO (terminal AO)
Modbus communications (terminals RS485+, RS485-, A0V)
Set Sinking Mode/Sourcing Mode
Close the circuit between terminals DIC-D24V and DIC-D0V to set the sinking mode/sourcing mode and the
internal/external power supply for the MFDI terminals. The default setting for the drive is internal power supply
sinking mode.
NOTICE: Do not close the circuit between terminals D24V and D0V. A closed circuit between these terminals will cause
damage to the drive.
Mode Internal Power Supply (Terminal D0V-D24V) External 24 V power supply
Sinking Mode
(NPN)
Sourcing Mode
(PNP)
Pulse Train Output
You can use pulse train monitor output terminal PO for sourcing mode or for sinking mode.
Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Load Impedance
R
L
(kΩ)
Output Voltage
V
PO
(V)
1.5 or more 5 Vor more
4.0 or more 8 Vor more
10 or more 10 Vor more
Note:
Use the formula below to calculate the necessary load resistance (kΩ) to increase output voltage V
PO
(V).

Table of Contents

Related product manuals