Parameter Details
12
12.8 L: PROTECTION
SIEPCYEUOQ2V01A Q2V Technical Manual 631
12.8 L: PROTECTION
L parameters set the following functions.
Motor Overload Protection
Operation During Momentary Power Loss
Stall Prevention
Speed Detection
Auto Restart
Detection of Overtorque/Undertorque
Torque Limit
Hardware Protection
L1: MOTOR PROTECTION
L1 parameters set the motor overload protection function.
Motor Protection Using Positive Temperature Coefficient (PTC) Thermistors
The temperature resistance characteristics of three PTC thermistors in the motor stator winding protect the motor
from overheat.
A PLC thermistor must have the characteristics shown below for each motor phase.
Figure 12.106 PTC Thermistor Temperature and Resistance
If the PTC input signal input to the drive is more than the overload alarm level, the drive detects oH3 [Motor
Overheat (PTC Input)]. The drive continues the operation set in L1-03 [Motor oH AL Reaction Select]. By
default, the keypad shows oH3 and the drive continues operation.
The overheat fault level triggers an oH4 [Motor Overheat Fault (PTC Input)] fault, and outputs a fault signal. The
drive outputs a fault signal and uses the stop method set in L1-04 [Motor oH FLT Reaction Select] to stop the
motor.
Note:
PTC is an acronym for Positive Temperature Coefficient.
L1-01: Motor Cool Type for OL1 Calc
No.
(Hex.)
Name Description
Default
(Range)
L1-01
(0480)
Motor Cool Type for OL1
Calc
Sets the motor overload protection with electronic thermal protectors.
Determined by A1-02
(0 - 6)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
Output Current
Output Frequency

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2V Series and is the answer not in the manual?

Omron Q2V Series Specifications

General IconGeneral
BrandOmron
ModelQ2V Series
CategoryInverter
LanguageEnglish

Related product manuals