12.1 A: INITIALIZATION
436 SIEPCYEUOQ2V01A Q2V Technical Manual
Note:
Usually, the keypad will not show A1-05. To show and set A1-05, show A1-04 [Password Input] and then push and on the
keypad at the same time.
After you set A1-05, the keypad will not show it again until you enter the correct password in A1-04. Make sure that you remember the
A1-05 setting value. If you do not know the A1-05 setting value, contact the manufacturer or your nearest sales representative.
When A1-03 = 2220, 3330 [2-Wire Initialization, 3-Wire Initialization], the drive is initialized to A1-05 = 0000. Be sure to set the
password again when a password is necessary for the application.
Change the setting value in A1-05 to change the password. The new setting value becomes the new password.
When you use the password to unlock and change a parameter, enter a value other than the password in A1-04 to lock the parameter
again with the same password.
If A1-04 A1-05, Modbus Communication cannot read or write A1-05.
A1-07: Q2pack Enable
No.
(Hex.)
Name Description
Default
(Range)
A1-07
(0128)
Q2pack Enable
Sets the drive to operate with Q2pack.
0
(0 - 2)
Q2pack is a simple visual programming tool that lets you connect function blocks to customize the drive and add
PLC functions.
Note:
Q2pack will overwrite drive settings when it uses MFDI/MFDO and MFAI/MFAO. When you use Q2pack to make changes to the
drive, the changes will stay after you disable Q2pack.
For more information about Q2pack, contact your nearest sales representative.
0 : Disable Q2pack
1 : Enable Q2pack
2 : With DI
Set H1-xx = 9F [MFDI Function Select = Q2pack Disable]. Deactivate the digital input to enable programs made
with Q2pack and activate the terminal to disable the programs.
A1-11: Firmware Update Lock
No.
(Hex.)
Name Description
Default
(Range)
A1-11
(111D)
Expert
Firmware Update Lock
Protects the drive firmware. When you enable the protection, you cannot update the drive
firmware.
0
(0, 1)
0 : Disabled
Lock is disabled.
1 : Enabled
Lock is enabled.
A1-12: Bluetooth ID
No.
(Hex.)
Name Description
Default
(Range)
A1-12
(1564)
Bluetooth ID
Sets the password necessary to use Bluetooth to control the drive with a smartphone or tablet.
-
(0000 - 9999)
A2: MANUAL SELECTION
You can register frequently used parameters and recently changed parameters here to access them quickly. Use
Setup Mode to show the saved parameters.
A2-01 to A2-32: MAN1 Param1 to MAN3 Param12
No.
(Hex.)
Name Description
Default
(Range)
A2-01 to A2-32
(0106 - 0125)
MAN1 Param1 to MAN3
Param12
You can select a maximum of 32 parameters for the drive and save the values to parameters A2-01
to A2-32. Use Setup Mode to show the saved parameters. You can immediately access these saved
parameters.
Parameters in General-
Purpose Setup Mode
(Determined by A1-07)