Startup Procedure and Test Run
4
4.8 Automatic Parameter Settings Optimized for Specific Applications (Application Presets)
SIEPCYEUOQ2V01A Q2V Technical Manual 123
4.8 Automatic Parameter Settings Optimized for Specific
Applications (Application Presets)
Show the frequency reference screen.
Note:
Press and hold a to return to frequency reference screen from any screen.
Use this procedure to set an application preset.
The drive has application presets to set the necessary parameters for different applications to their best values. Use
to find parameters that were changed automatically by the application preset function in A1-06.
Note:
Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Init Parameters = 2-Wire Initialization, 3-Wire Initialization] to
initialize parameters.
Figure 4.21 Automatic Parameter Settings
Press and hold to go back to the frequency reference screen.
Note:
Make sure that you do Auto-Tuning after you set A1-06 for a hoist application.
It is not possible to change the A1-06 value. To set an application preset, first set A1-03 = 2220 to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
When the drive changes to the A1-06 setting, it will also reset the parameters automatically registered to A2-17 to A2-32 [MAN2
Param7 to MAN3 Param12] when A2-33 = 1 [Manual Autoset Parameters = Auto Save].