Parameter List
11
11.12 o: KEYPAD
SIEPCYEUOQ2V01A Q2V Technical Manual 383
◆ o2: KEYPAD OPERATION
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o2-01
(0505)
LO/RE Key Selection of
Function
Sets the function that lets you use to switch between LOCAL and REMOTE
Modes.
0 : Disabled
1 : Enabled
1
(0, 1)
701
o2-02
(0506)
STOP Key Selection of
Function
Sets the function to use on the keypad to stop the drive when the Run
command source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
702
o2-03
(0507)
UserPar Set Default
Values
Sets the function to keep the settings of changed parameters as user parameter defaults
to use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
0
(0 - 2)
702
o2-04
(0508)
Drive KVA Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
702
o2-05
(0509)
LCD FreqRef
Mode@Home Screen
Sets the function that makes it necessary to push to use the keypad to change the
frequency reference value while in Drive Mode.
0 : Disabled
1 : Enabled
0
(0, 1)
703
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable
from the drive or if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
0
(0, 1)
703
o2-07
(0527)
Keypad Dir@Power-Up
Sets the direction of motor rotation when the drive is energized and the keypad is the
Run command source.
0 : Forward
1 : Reverse
0
(0, 1)
703
o2-09
(050D)
Region Code for
Initialization
- - 704
o2-19
(061F)
Expert
Parameter Write during
Uv
Lets you change parameters during Uv [Undervoltage].
0 : Disable
1 : Enable
0
( 0, 1 )
704
o2-23
(11F8)
RUN
Ext24V Off Warning
Display
Sets the function to give a warning if the backup external 24 V power supply turns off
when the main circuit power supply is in operation.
0 : Disabled
1 : Enabled
0
(0, 1)
704
o2-26
(1563)
Ext24V Mode Warning
Display
When you connect a backup external 24 V power supply, this parameter sets the
function to trigger an alarm when the main circuit power supply voltage decreases.
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : Disabled
1 : Enabled
0
(0, 1)
704
o2-27
(1565)
BLE Disconn.
Selection@BLE Ctrl
Sets drive operation if the Bluetooth device is disconnected when you operate the drive
in Bluetooth Mode.
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
4 : No Alarm Display
3
(0 - 4)
704