Parameter List
11
11.4 b: APPLICATION
SIEPCYEUOQ2V01A Q2V Technical Manual 325
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-90
(0B90)
EZsleep Unit
Sets the measurement units for b5-91 [EZsleep Min Spd] and b5-92 [EZsleep Level].
0 : rpm
1 : 0.1Hz units
0
(0, 1)
481
b5-91
(0B91)
RUN
EZsleep Min Spd
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the
largest value from b5-91, b5-34 [PID Out Low Limit Level], and d2-02 [FRef Lower
Limit].
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
481
b5-92
(0B92)
RUN
EZsleep Level
Sets the value that the output frequency or motor speed must be less than for longer than
b5-93 [EZsleep Time] to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
481
b5-93
(0B93)
RUN
EZsleep Time
Sets the length of time that the output frequency or motor speed must be less than b5-92
[EZsleep Level] to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
481
b5-94
(0B94)
RUN
EZsleep Wake Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
0.00%
(0.00 - 600.00%)
481
b5-95
(0B95)
EZsleep Wake Mode
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Setpoint Delta
1 : Absolute
0
(0, 1)
482
b5-96
(0B96)
RUN
EZsleep Wake Time
Sets the EZ Wake-up time.
1.0 s
(0.0 - 1000.0 s)
482
◆ b6: DWELL FUNCTION
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b6-01
(01B6)
Dwell Ref.@Start
Sets the output frequency that the drive will hold momentarily when the motor starts.
0.0
(Determined by A1-02)
482
b6-02
(01B7)
Dwell Time@Start
Sets the length of time that the drive will hold the output frequency when the motor
starts.
0.0 s
(0.0 - 10.0 s)
483
b6-03
(01B8)
Dwell Ref@Stop
Sets the output frequency that the drive will hold momentarily when ramping to stop the
motor.
0.0
(Determined by A1-02)
483
b6-04
(01B9)
Dwell Time@Stop
Sets the length of time for the drive to hold the output frequency when ramping to stop
the motor.
0.0 s
(0.0 - 10.0 s)
483
◆ b8: ENERGY SAVING
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b8-01
(01CC)
eSave Ctrl Selection
Sets the Energy-saving control function.
0 : Disabled
1 : Enabled
2 : Search Enabled
Note:
When A1-02 = 6 [Control Method = PM AOLVector], you can only select setting 2
in Expert Mode.
0
(0 - 2)
483
b8-02
(01CD)
RUN
Expert
eSave Ctrl Gain
Sets the gain for Energy-saving control.
Determined by A1-02
(0.0 - 10.0)
483
b8-03
(01CE)
RUN
Expert
eSave Filter Time
Sets the responsiveness for Energy-saving control.
Determined by A1-02,
C6-01 and o2-04
(0.00 - 10.00 s)
484
b8-04
(01CF)
Expert
eSave Coef. Value
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The
default setting is for Yaskawa motors.
Determined by C6-01,
E2-11, and o2-04
(0.00 - 655.00)
484