11.20 Defaults by Drive Model and Duty Rating ND/HD
416 SIEPCYEUOQ2V01A Q2V Technical Manual
◆ Three-Phase 400 V Class
No.
*1
Name Unit Default
- Drive Model - 4001 4002 4004 4005
C6-01
ND/HD Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive KVA
Selection
Hex. 91 92 93 94
E2-11
(E4-11, E5-
02)
Motor Rated
Power (kW)
kW 0.2 0.4 0.4 0.75 0.75 1.5 1.5 2.2
b3-04
SpSrch V/F
Gain
% 100 100 100 100 100 100 100 100
b3-06
Speed Curr
Lev1 for
Estimation
- 1.0 1.0 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed ACR
PGain for
Estimation
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Dir. Determ.
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
eSave Filter
Time
s 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04
eSave Coef.
Value
- 713.8 576.4 576.4 447.4 447.4 338.8 338.8 313.6
C6-02
Carrier
Frequency
Selection
- 3 7 3 7 3 7 3 7
E2-01
(E4-01)
Mot Rated
Current (FLA)
A 0.6 1 1 1.6 1.6 3.1 3.1 4.2
E2-02
(E4-02)
Mot Rated
Slip
Hz 2.5 2.9 2.9 2.6 2.6 2.5 2.5 3
E2-03
(E4-03)
Mot No-Load
Current
A 0.4 0.6 0.6 0.8 0.8 1.4 1.4 1.5
E2-05
(E4-05)
Motor L-L
Resistance
Ω 83.94 38.198 38.198 22.459 22.459 10.1 10.1 6.495
E2-06
(E4-06)
Motor Leak
Inductance
% 21.9 18.2 18.2 14.3 14.3 18.3 18.3 18.7
E2-10
(E4-10)
Motor Iron
Loss
W 12 14 14 26 26 53 53 77
E5-01
PM Mot Code
Selection
- FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
RideThrough
Time@Power
Loss
s 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3
L2-03
Min Baseblck
Time
s 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.5
L2-04
Powloss
Ramp
Time@recov
ery
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
UV Detection
Lvl (Uv1)
- 380 380 380 380 380 380 380 380
L3-02
StallP
Level@Accel
% 150 120 150 120 150 120 150 120
L3-06
StallP
Level@Run
% 150 120 150 120 150 120 150 120
L3-24
Acc@Rated
Torque
s 0.178 0.178 0.178 0.142 0.142 0.166 0.166 0.145
L8-02
Overheat Alm
Level
°C 120 120 120 120 105 105 90 90
L8-09
Ground Fault
Selection
- 0 0 0 0 0 0 0 0
n1-03
HuntPrev
Time Constant
ms 10 10 10 10 10 10 10 10