Parameter Details
12
12.8 L: PROTECTION
SIEPCYEUOQ2V01A Q2V Technical Manual 667
L7-03: FW Reg. TrqLimit
No.
(Hex.)
Name Description
Default
(Range)
L7-03
(04A9)
RUN
FW Reg. TrqLimit
Sets the torque limit value for forward regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
Note:
The lower torque limit is enabled when you set the torque limit by the following method.
Set H3-02 or H3-10 = 9, D [MFAI Function Select = FW Trq Lim, GenerTrqLim].
Use a communication option to set the torque limits
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
If you set the value too low with large loads, the motor can stall.
L7-04: RV Reg. TrqLimit
No.
(Hex.)
Name Description
Default
(Range)
L7-04
(04AA)
RUN
RV Reg. TrqLimit
Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
Note:
Use this method to set the torque limit and enable the lower torque limit:
Set H3-02 or H3-10 = 9, D [MFAI Function Select = FW Trq Lim, GenerTrqLim].
Use a communication option to set the torque limits
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
If you set the value too low with large loads, the motor can stall.
L7-06: TrqLimit Integral Time
No.
(Hex.)
Name Description
Default
(Range)
L7-06
(04AC)
TrqLimit Integral Time
Sets the integral time constant for the torque limit function.
200 ms
(5 - 10000 ms)
Decrease the setting value to increase torque limit responsiveness when you use torque limits and L7-07 = 2
[TrqLimit@Acc/Decel = I-ctrl@Ac/Dec].
If there is hunting when torque limits are active, increase the setting value.
L7-07: TrqLimit@Acc/Decel
No.
(Hex.)
Name Description
Default
(Range)
L7-07
(04C9)
TrqLimit@Acc/Decel
Sets the torque limit function during acceleration and deceleration.
1
(1, 2)
1 : P-ctrl@Ac/Dec
The torque limit function works with proportional control during acceleration and deceleration, and switches to
integral control at constant speed. Use this setting when quickly reaching the target speed is more important than
the torque limit during speed changes.
2 : I-ctrl@Ac/Dec
The torque limit function always uses integral control. Use this setting when a very accurate torque limit is
necessary during speed changes, for example in winding machine applications.
If you make the torque limit the most important, it can:
Increase the acceleration and deceleration times.
Not let the motor speed reach the frequency reference value during run at constant speed.