3 Operation
High-function General-purpose Inverter RX2 Series User’s Manual
3-8 Parameter Function
3
3-8-1 Parameter Preservation Function
3-8 Parameter Function
By configuring the soft-lock function you can prevent parameters from being changed.
Parameters
3-8-1 Parameter Preservation Function
Item Parameter Data Description
Soft-lock selection [UA-16] 00 Normal state.
Only when the soft-lock terminal [SFT] is on, data set to
[UA-17] other than [UA-16] are locked.
01 After the setting is performed, the data set to [UA-17] other
than [UA-16] are locked.
Soft-lock target
selection
[UA-17] 00 All data other than [UA-16] cannot be changed
01 Data other than [UA-16] and set frequency cannot be changed
Input terminal
selection
[CA-01] to
[CA-11]
036 [SFT]: Used when the soft-lock function is used on terminals.
Menu
Optional
device
60.00Hz
oFW
STOP
M1
H03
Output Frequency
0.00 Hz
UA-16
Soft-Lock Selection
01: Always enabled
LKS
By configuring the soft-lock function [UA-16] and [UA-17], you
can prevent parameters from being changed.
While soft-lock function is enabled, the LKS mark (Lock State
mark) is shown on the right of parameters.