4 - 7
4 Test Run
High-function General-purpose Inverter RX2 Series User’s Manual
4-4 Conduct a Test Run with Analog Input
4
4-4 Conduct a Test Run with Analog Input
This section describes how to conduct a test run, using variable resistance knobs into terminal block
[FW] input and analog input H, Ai1 and L.
To perform a test run using analog input Ai1, set the following parameters from the initial value, or
check the following parameters.
(a) Frequency command source selection [AA101]
(b) Main speed command [FA-01]
(c) Operation command source selection [AA111]
(d) Setting the electronic thermal level of motor [bC110]
A test run can be performed using a variable resistor.
A test run can be performed with 10 V voltage input.
Procedure
From the initial screen displayed at power-on, move to “H03” with the LEFT/RIGHT arrow ( )
keys.
For procedure of changing parameters, see 3-2-1 Scroll Mode on page 3-14.
1 Frequency command source selection [AA101]
Set the frequency command source to “01:Ai1 input”.
Menu
Option
0.00Hz
oFW
STOP
M1
H03
Output Frequency
0.00 Hz
AA101
01 [Ai1] terminal