5 Monitor
5 - 22
High-function General-purpose Inverter RX2 Series User’s Manual
5-13 Inverter Status Monitor
Displays the current conditions of inverter.
Precautions for Correct Use
Command destinations vary according to the state of terminal functions as well as to the set-
tings. Commands not input from the currently enabled command destinations will be ignored.
Parameter
Detailed Monitor for Icon 2 LIM [dC-37]
Detailed Monitor for Icon 2 ALT [dC-38]
Item Parameter Data Description
Detailed monitor for
icon 2 LIM
[dC-37] 00 to 06
Refer to 3-1-3 LCD Display on page 3-5.
Detailed monitor for
icon 2 ALT
[dC-38] 00 to 04
Detailed monitor for
icon 2 RETRY
[dC-39] 00 to 02
Detailed monitor for
icon 2 NRDY
[dC-40] 00 to 05
Data Status Description
01
The overcurrent suppression function is applied due to
increased current.
Under overcurrent suppression.
02
The overload limiting function is applied due to increased cur-
rent.
Under overload limit.
03
The overvoltage suppression function is applied due to
increased P-N voltage.
Under overvoltage suppression.
04
The torque limiting function is applied due to increased cur-
rent.
Under torque limit.
05
The frequency is within the upper/lower limit or jump frequency
limit.
Within upper limit.
Within lower limit.
Within jump frequency limit.
06
The frequency command at below the minimum frequency has
been given.
Under minimum frequency limit.
00 A state other than those above. A state other than those above.
Data Status Description
01 Current is increased.
Overload advance notice in
effect.
02 The motor thermal load is increased.
Motor thermal advance notice in
effect.
03 The inverter thermal load is increased.
Inverter thermal advance notice
in effect.
04 Motor temperature is rising.
Motor heating advance notice in
effect.
00 A state other than those above. A state other than those above.