13 Maintenance and Inspection
13 - 4
High-function General-purpose Inverter RX2 Series User’s Manual
13-3 Inspection Items
Target
section
Item Details
Interval
Method Criteria
Mea-
sure-
ment
instru-
ment
Daily
Periodic
1
year
2
years
General
Ambient
environment
Check the ambi-
ent temperature,
humidity, dust,
etc.
See the installation
method.
The ambient tem-
perature and humidity
are within the usable
range. No freezing,
condensation, dust,
corrosive gas, explo-
sive gas, flammable
gas, mist of grinding
fluid, hydrogen sul-
fide, and salts are
permissible
Ther-
mometer
Hydrom-
eter
Recorder
Entire device
No abnormal
vibration or
sound is
observed.
By visual check and
hearing
There must be no
abnormality.
Power supply
voltage
The main circuit
voltage is normal.
Measure line volt-
age between
inverter main circuit
terminals R, S, and
T.
They are within the
allowable variation
range of AC voltage.
Test er
and
digital
multime-
ter