8 - 175
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-11 Output Terminal Function
8
8-11-2 Output Terminal NO/NC Selections
You can set output specifications for Contact a or Contact b separately for Output terminals 11 to 15
and Relay output terminals 16 and 17.
Parameter
• Contact a: Closes with “ON,” and opens with “OFF.”
• Contact b: Closes with “OFF,” and opens with “ON.”
062 LOG1 Result of logical operation 1 P. 8-151
063 LOG2 Result of logical operation 2 P. 8-151
064 LOG3 Result of logical operation 3 P. 8-151
065 LOG4 Result of logical operation 4 P. 8-151
066 LOG5 Result of logical operation 5 P. 8-151
067 LOG6 Result of logical operation 6 P. 8-151
068 LOG7 Result of logical operation 7 P. 8-151
069 MO1 General purpose output 1 P. 8-173
070 MO2 General purpose output 2 P. 8-173
071 MO3 General purpose output 3 P. 8-173
072 MO4 General purpose output 4 P. 8-173
073 MO5 General purpose output 5 P. 8-173
074 MO6 General purpose output 6 P. 8-173
075 MO7 General purpose output 7 P. 8-173
076 EMFC During-Em-Force signal P. 8-94
077 EMBP During-bypass-mode signal P. 8-96
080 LBK Flat battery of LCD operator P. 3-48
081 OVS Excessive voltage of accepted power P. 8-139
084 AC0 Alarm code bit 0 P. 8-126
085 AC1 Alarm code bit 1 P. 8-126
086 AC2 Alarm code bit 2 P. 8-126
087 AC3 Alarm code bit 3 P. 8-126
089 OD3 PID3 excessive deviation P. 8-33
090 FBV3 PID3 feedback comparison P. 8-34
091 OD4 PID4 excessive deviation P. 8-33
092 FBV4 PID4 feedback comparison P. 8-34
093 SSE PID soft start abnormality P. 8-20
8-11-2 Output Terminal NO/NC Selections
Item Parameter Data Description
Output terminal func-
tion selection
[CC-11] to
[CC-15]
00, 01
00: Contact a (normally open) operation
01: Contact b (normally closed) operation
Relay output terminal
function selection a/b
(NO/NC) selection
[CC-16]
Relay output terminal
function selection a/b
(NO/NC) selection
[CC-17]
Function No. Abbreviation Function name Page