EasyManuals Logo

Omron RX2 Series User Manual

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #381 background imageLoading...
Page #381 background image
7 - 73
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-5 Start Conditions
7
7-5-5 Starting after Power-on
(Ex.) Frequency matching operation after reset [RS]
Note If the frequency matching after reset has been set, starting after power-on will also occur with frequency
matching.
Sets the start mode at power-on.
(Ex.1) Restart operation with 0 Hz: [bb-41]=00
(Ex.2) Frequency pull-in operation [bb-41]=01 to 03
Frequency Matching After Reset [RS] [bb-41]=02
Item Parameter Data Description
Default
data
Restart mode after
RS release
[bb-41] 02 Performs frequency pull-in restart. 00
Retry wait time
before motor
restart
[bb-26] 0.3 to 100.0(s) Sets the wait time after the operation command. 0.3
7-5-5 Starting after Power-on
0
[bb-26]
[bb-42]
Free-running
Restarting with frequency pull-in
Operation
command FW
Reset RS
Motor speed
Restart with 0 Hz
Input power
Operation
command
Motor speed
[bb-26]
Free-running
Follows [bb-41]
Input power
Operation
command
Motor speed

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron RX2 Series and is the answer not in the manual?

Omron RX2 Series Specifications

General IconGeneral
BrandOmron
ModelRX2 Series
CategoryInverter
LanguageEnglish

Related product manuals