7 - 73
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-5 Start Conditions
7
7-5-5 Starting after Power-on
(Ex.) Frequency matching operation after reset [RS]
Note If the frequency matching after reset has been set, starting after power-on will also occur with frequency
matching.
Sets the start mode at power-on.
(Ex.1) Restart operation with 0 Hz: [bb-41]=00
(Ex.2) Frequency pull-in operation [bb-41]=01 to 03
Frequency Matching After Reset [RS] [bb-41]=02
Item Parameter Data Description
Default
data
Restart mode after
RS release
[bb-41] 02 Performs frequency pull-in restart. 00
Retry wait time
before motor
restart
[bb-26] 0.3 to 100.0(s) Sets the wait time after the operation command. 0.3
7-5-5 Starting after Power-on
Free-running
Restarting with frequency pull-in
Operation
command FW
Reset RS
Motor speed
Restart with 0 Hz
Input power
Operation
command
Motor speed
Free-running
Follows [bb-41]
Input power
Operation
command
Motor speed