EasyManua.ls Logo

Omron RX2 Series - Page 380

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Advanced Settings
7 - 72
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.) Retry operation on overvoltage
(Ex.) Frequency matching operation after free-run stop [FRS]
Retry on Overvoltage [bb-30]=01
Item Parameter Data Description
Default
data
Selection of restart
mode @over-volt-
age
[bb-30] 02 Performs frequency pull-in restart. 01
Wait time of restart
@over-voltage
[bb-31] 0.3 to 100.0(s) Sets the wait time after the operation command. 0.3
Frequency Matching After Free-run Stop [FRS] [bb-40]=02
Item Parameter Data Description
Default
data
Restart mode after
FRS release
[bb-40] 02 Performs frequency pull-in restart. 00
Retry wait time
before motor
restart
[bb-26] 0.3 to 100.0(s) Sets the wait time after the operation command. 0.3
0
[bb-31]
[bb-42]
Free-running
Restarting with frequency pull-in
Operation
command FW
Voltage between
P and N
Motor speed
Overcurrent occurs
0
[bb-26]
[bb-42]
Free-running
Restarting with frequency pull-in
Operation
command FW
Free-run
stop FRS
Motor speed

Table of Contents

Related product manuals