7 Advanced Settings
7 - 72
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.) Retry operation on overvoltage
(Ex.) Frequency matching operation after free-run stop [FRS]
Retry on Overvoltage [bb-30]=01
Item Parameter Data Description
Default
data
Selection of restart
mode @over-volt-
age
[bb-30] 02 Performs frequency pull-in restart. 01
Wait time of restart
@over-voltage
[bb-31] 0.3 to 100.0(s) Sets the wait time after the operation command. 0.3
Frequency Matching After Free-run Stop [FRS] [bb-40]=02
Item Parameter Data Description
Default
data
Restart mode after
FRS release
[bb-40] 02 Performs frequency pull-in restart. 00
Retry wait time
before motor
restart
[bb-26] 0.3 to 100.0(s) Sets the wait time after the operation command. 0.3
Free-running
Restarting with frequency pull-in
Operation
command FW
Voltage between
P and N
Motor speed
Overcurrent occurs
Free-running
Restarting with frequency pull-in
Operation
command FW
Free-run
stop FRS
Motor speed