3 - 49
3 Operation
High-function General-purpose Inverter RX2 Series User’s Manual
3-11 Preventing Read and Write of Unnecessary Data
3
3-11 Preventing Read and Write of
Unnecessary Data
You can configure the prohibition of data reading and writing via LCD operator.
By setting [UA-18] Data R/W selection to 01, Read/Write access from LCD operator is disabled, and
read and write of unnecessary data can be prevented.
After the parameter is confirmed, if it is set to 01 after data is read for backup, unnecessary read and
write can be prevented.
Parameter
Item Parameter Data Description
Data R/W selection [UA-18] 00 R/W enabled. Read and write are possible.
01 R/W disabled. Read and write are prohibited.