7 Advanced Settings
7 - 74
High-function General-purpose Inverter RX2 Series User’s Manual
Precautions for Correct Use
• The operation at power-on is the same as that of the restart after reset stop which occurs
when the inverter recovers from reset.
• If the frequency pull-in restart is used, the rotational direction of the output frequency is the
same as that of the frequency command.
• If a power failure lasts long and the inverter’s internal power supply is lost, recovery will take
place by the restart after reset instead of the restart after instantaneous power fail-
ure/under-voltage.
• In the case of [bb-41]=01, if the residual voltage generated by the motor cannot be detected,
the 0 Hz restart may take place.
Parameter
Set the start mode after a trip reset or a reset input via the [RS] terminal (input terminal function 028).
(Ex.1) Restart operation with 0 Hz: [bb-41]=00
Item Parameter Data Description
Default
data
Restart mode after
RS release
[bb-41]
00 Performs the 0 Hz restart.
00
01
Performs frequency matching restart.
*1
*1. See 7-5-3 Frequency Matching Start on page 7-65.
02
Performs frequency pull-in restart.
*2
*2. See 7-5-4 Frequency Pull-in Start on page 7-69.
03
Restarts from the speed received from Input
terminal A and B or the PG option unit.
Retry wait time
before motor
restart
[bb-26] 0.3 to 100.0(s)
Sets the wait time after the operation com-
mand.
0.3
7-5-6 Restart after Releasing Reset
Restart with 0
[RS] Reset
Operation
command
Motor speed