3 Operation
3 - 50
High-function General-purpose Inverter RX2 Series User’s Manual
3-12 Inverter Initialization
When the initialization target [Ub-01] is chosen and [Ub-05] Start Initialization is set to 01, the desig-
nated data can be initialized to the factory setting.
Only the trip history can be cleared without initialization of the stored parameter values.
Precautions for Correct Use
Duty type selection (Ub-03) is not initialized.
The initialization sets the parameters to initial values. If the data before the initialization are
necessary, read the data using the R/W function (Read) on the operator keypad or use PC
software to save the data on a PC.
The parameter for initialization is not displayed, depending on the setting of Display Restric-
tion Selection (UA-10). Set the initial values to 00 (Full display) to complete the initialization.
The initialization cannot be achieved when a change of the parameter setting values is
banned on the setting of Soft Lock Selection (UA-16). Be sure to perform the initialization
after the banned change of the parameter setting values is reset.
Take a caution that the initialization starts when you set data of Initialize Enable (Ub-05) to 01
(Start initialization) and press F2 key. The previous data cannot be returned.
Parameter
Item Parameter Data Description
Initialize
Mode
selection
[Ub-01]
00 The initialization is disabled.
01 The trip history and retry history are cleared.
02 All the parameters are all initialized.
03 The trip history, retry history, and all parameters are initialized.
04
The trip history, retry history, all parameters, and program data for
DrivePrograming are initialized.
05 Parameters other than those of I/O terminal function are initialized.
06
Parameters other than the communication function parameters are
initialized.
07
Parameters other than those of I/O terminal function and communica-
tion function are initialized.
08 Only the program data for DriveProgramming are initialized.
Initialize
Data
selection
[Ub-02] 01 Mode 1 (the factory setting)
Initialize
Enable
[Ub-05]
00 Function disabled
01 Initialization start