EasyManua.ls Logo

Omron RX2 Series - Explanation of each Function Code

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - 9
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-3 Explanation of Each Function Code
9
9-3 Explanation of Each Function Code
Reads the coil status (ON/OFF).
Precautions for Correct UsePrecautions for Correct Use
The byte order was changed when data over 1 bite is processed with reading function of sev-
eral coils via Modbus communication.
Receive data in the data layout as shown below, according to the number of data bytes to be
read.
Data received as 1-byte data (1 to 8 coils)
Data received as 2-byte data (9 to 16 coils)
Data received as 3-byte data (17 to 24 coils)
Data received as 4-byte data (25 to 32 coils)
Example
When inverter’s input terminal function 1 to 6 with slave address 8 is read out
, the input terminal status
is shown as below table.
Coil numbers 000B hex and 000C hex are OFF.
Read Coil Status [01 hex]
Coil 8 to Coil 1
Coil 8 to Coil 1 Coil 16 to Coil 9
Coil 8 to Coil 1 Coil 16 to Coil 9 Coil 24 to Coil 17
Coil 8 to Coil 1 Coil 16 to Coil 9 Coil 24 to Coil 17 Coil 32 to Coil 25
Item Data
Input terminal No. 1 2 3 4 5 6
Coil number 0005 hex 0006 hex 0007 hex 0008 hex 0009 hex 000A hex
Terminal status ON ON ON OFF ON OFF

Table of Contents

Related product manuals