6 - 19
6 Basic Parameter Settings
High-function General-purpose Inverter RX2 Series User’s Manual
6-3 Operation Command Settings
6
6-3-1 Types of Operation Commands
6-3 Operation Command Settings
The operation command (operation modes) selected in a function is enabled.
For details, see the description in the next and subsequent sections.
Precautions for Correct Use
The operation of the inverter requires not only an operation command but also a frequency
command.
Precautions for Correct Use
• The above shows an example of operation with [AA111]=02 (RUN key on the LCD operator).
• Functions not assigned to the input terminal functions [CA-01]-[CA-11] become OFF.
The LCD operator is used to give a frequency command.
Use “RUN Key” and “STOP/RESET Key” for operation and stop respectively.
For operation using the LCD operator, the operation direction can be changed by setting RUN-key
Direction of LCD operator, 1st-motor [AA-12].
Precautions for Correct Use
• The output of the inverter requires not only an operation command but also a frequency com-
mand.
• If the forced operation 023 [F-OP] of the terminal function is enabled, the command destina-
tion specified in the [F-OP] function becomes effective irrespective of the present setting.
6-3-1 Types of Operation Commands
6-3-2 Operation with LCD Operator
[CA-71]
(00-06)
[AA111]
(00-06)
F-OP
selection
Run-command
input source
selection,
1st-motor
Operation
command.
Forced
operation
parameter setting data
CA-71
AA111
00: [FW]/[RV] terminal
01: 3 wire
02: RUN key on LCD Operator
03: RS485
04: Option 1
05: Option 2
06: Option 3