6 Basic Parameter Settings
6 - 18
High-function General-purpose Inverter RX2 Series User’s Manual
Use IVMS control when a high torque is required for activation while you use SM/PMM motors.
Precautions for Correct Use
If a high torque is necessary for activation, original IVMS control is used. If 03 is chosen for
the auto-tuning selection [HA-01], it can be detected whether the target motor can be driven
with the IVMS control, although combination check should be made in advance.
The tuning with the IVMS control should be performed on an independent motor with the
Control mode selection, 1st-motor [AA121] set to 12 (SM/PMM: IVMS activation).
In case of failure of the auto-tuning with the IVMS control, data necessary for the IVMS con-
trol cannot be obtained from the motor and the Control mode selection, 1st-motor [AA121]
should be set to 11 (SM/PMM: Synchronous activation) to drive the motor.
IVMS Auto-tuning