8 Applied Settings
8 - 62
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.3) When [bb-23] ≠00 and [bb-30] = 01, it restarts by picking up the frequency.
See 7-5-3 Frequency Matching Start on page 7-65 for details.
(Ex.4) When [bb-23] ≠00 and [bb-30] = 02, it restarts with frequency pull-in.
See 7-5-4 Frequency Pull-in Start on page 7-69 for details.
(Ex.5) When [bb-23] ≠00 and [bb-30] = 03, it restarts using the motor speed feedback.
For motor speed feedback, the feedback input to the input terminals A and B, or feedback input to the
optional cassette PG option unit is required.