EasyManua.ls Logo

Omron RX2 Series - Page 564

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Applied Settings
8 - 164
High-function General-purpose Inverter RX2 Series User’s Manual
The following table is a relation between Analog Input Ai2 and Frequency Command.
Relation between Analog Input Ai2 and Frequency Command
Item Parameter Data Description
Default
data
Filter time constant of
Terminal [Ai2]
[Cb-11] 1 to 500(ms) Filters the input. 16
Start value of Terminal
[Ai2]
[Cb-13]
0.00
to 100.00(%)
Sets a frequency instruction ratio when set-
ting a start ratio for analog input.
0.00
End value of Terminal
[Ai2]
[Cb-14]
0.00
to 100.00(%)
Sets a frequency instruction ratio when set-
ting an end ratio for analog input.
100.00
Start rate of Terminal
[Ai2]
[Cb-15]
0.0
to [Cb-16](%)
With respect to a minimum ratio for analog
input for 0 to 10 V/0 to 20 mA, sets a start
ratio.
20.0
End rate of Terminal
[Ai2]
[Cb-16]
[Cb-17]
to 100.0(%)
With respect to an external frequency
instruction for 0 to 10 V, 0 to 20 mA, sets an
end ratio.
100.0
Start point selection of
Terminal [Ai2]
[Cb-17]
00
For an instruction for a value of one of
0.00% to the “Start amount [Cb-13]” and to
the “End amount [Cb-14],” whichever is
lower, one of the values of the “Start amount
[Cb-13]” and the “End amount [Cb-14],”
whichever is lower, is output.
01
01
For an instruction for a value of one of
0.00% to the “Start amount [Cb-13]” and to
the “End amount [Cb-14],” whichever is
lower, a value of 0.00% is output.
[Cb-04]
[Cb-03]
0
[Cb-06]
[Cb-05]
100
(0V/0mA) (10V/20mA)
(V/ mA)
[Cb-03]
[Cb-04]
0
[Cb-05]
[Cb-06]
100
(0V/0mA) (10V/20mA)
(V/ mA)
[Cb-04]
[Cb-03]
0
[Cb-05] [Cb-06] 100
(0V/0mA) (10V/20mA)
(V/ mA)
[Cb-04]
[Cb-03]
0
[Cb-05] [Cb-06] 100
(0V/0mA) (10V/20mA)
(V/ mA)
(Ex.1-1) [Cb-07]=00 (Ex.2-1) [Cb-07]=01
(Ex.1-2) [Cb-07]=00 (Ex.2-2) [Cb-07]=01
Maximum
frequency
The output frequency
for 0% to [Cb-05] is
[Cb-03].
Analog input
The output frequency
for [Cb-06] to 100% is
[Cb-04].
The output frequency
for 0% to [Cb-05] is 0
Hz.
The output frequency
for [Cb-06] to 100% is 0
Hz.
Analog input
Analog input
Analog input
Maximum
frequency
Maximum
frequency
Maximum
frequency

Table of Contents

Related product manuals