C - 51
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-3 Parameter List
C
Code
Codes that
can be
changed
during
operation
Name Data range
Initial
value
Note
Cd-01 -
[FM] monitor output wave form selec-
tion
00 (PWM)/01 (frequency) 00
Cd-02 -
[FM] monitor output base frequency (at
PWM output)
0 to 3600 (Hz) 2880
Cd-03 [FM] monitor output selection
See the <List of output monitor functions> on page
C-52
[dA-01]
Cd-04 [Ao1] monitor output selection
See the <List of output monitor functions> on page
C-52
[dA-01]
Cd-05 [Ao2] monitor output selection
See the <List of output monitor functions> on page
C-52
[dA-01]
Cd-10 -
Analog monitor adjustment mode
enable
00 (Disabled)/01 (Enabled) 00
Cd-11 - Filter time constant of [FM]monitor 1 to 500 (ms) 100
Cd-12 - [FM] Data type selection 00 (absolute value)/01 (with sign)00
Cd-13 [FM] monitor bias adjustment -100.0 to 100.0 (%) 0.0
Cd-14 [FM] monitor gain adjustment -1000.0 to 1000.0 (%) 100.0
Cd-15
Output level setting at [FM] monitor
adjust mode
-100.0 to 100.0 (%) 100.0
Cd-21 - Filter time constant of [Ao1] monitor 1 to 500 (ms) 100
Cd-22 - [Ao1] Data type selection 00 (absolute value)/01 (with sign) 00
Cd-23 [Ao1] monitor bias adjustment -100.0 to 100.0 (%) 0.0
Cd-24 [Ao1] monitor gain adjustment -1000.0 to 1000.0 (%) 100.0
Cd-25
Output level setting at [Ao1] monitor
adjust mode
-100.0 to 100.0 (%) 100.0
Cd-31 - Filter time constant of [Ao2] monitor 1 to 500 (ms) 100
Cd-32 - [Ao2] data type selection 00 (absolute value)/01 (with sign) 00
Cd-33 [Ao2] monitor bias adjustment -100.0 to 100.0 (%) 20.0
Cd-34 [Ao2] monitor gain adjustment -1000.0 to 1000.0 (%) 80.0
Cd-35
Output level setting at [Ao2] monitor
adjust mode
-100.0 to 100.0 (%) 100.0

Table of Contents