Motor temperature monitoring using a temperature sensor (Page320)
Motor protection by calculating the temperature (Page323)
Motor and converter protection by limiting the voltage (Page325)
The monitoring of the driven load prevents impermissible operating modes, e.g. dry-running
of a pump.
Monitoring the driven load (Page327)
Energy saving
The converter can optimize the e󹪟ciency of the motor.
E󹪟ciency optimization (Page334)
The converter calculates how much energy controlled converter operation saves when
compared to mechanical 󹪞ow control (e.g. throttle).
Calculating the energy saving for 󹪞uid 󹪞ow machines (Page337)
7.2 Sequence control when switching the motor on and o󹪜
Overview
The sequence control de󹪝nes the rules for switching the motor on and o󹪜.
5HDG\WRVZLWFKRQ
2SHUDWLRQ
2))21
After switching the supply voltage on, the converter normally goes into the "ready to start"
state. In this state, the converter waits for the command to switch on the motor.
The converter switches on the motor with the ON command. The converter changes to the
"Operation" state.
After the OFF1 command, the converter brakes the motor down to standstill. The converter
switches o󹪜 the motor once standstill has been reached. The converter is again "ready to
start".
Requirement
Functions
In order to be able to respond to external commands, you must set the command interface
so that it 󹪝ts your speci󹪝c application.
Tools
To change the function settings, you can use a commissioning tool.
$
%
&
Advanced commissioning
7.2Sequence control when switching the motor on and o󹪜
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 131