Who may perform the acceptance test of the converter?
Personnel from the machine manufacturer, who, on account of their technical qualications
and knowledge of the safety functions, are in a position to perform the acceptance test in the
correct manner are authorized to perform the acceptance testing of the converter.
Wizard for the acceptance test
The "Startdrive Advanced" commissioning tool (requires an appropriate license) includes a
wizard for the acceptance test of the safety functions integrated in the drive.
"Startdrive Advanced" guides you through the acceptance test, generates the appropriate
traces to analyze the machine response – and generates an acceptance report as Excel le.
Further information is provided on the Internet:
Startdrive, system requirements and download (https://
support.industry.siemens.com/cs/ww/en/view/109771710) (Startdrive, system requirements
and download)
Reduced acceptance test after function expansions
A full acceptance test is necessary only after rst commissioning. A reduced acceptance test
is sucient when safety functions are expanded.
Measure Acceptance test
Acceptance test Documentation
Functional expansion of the ma‐
chine (additional drive).
Yes.
Only check the safety
functions of the new
drive.
• Supplement machine overview
• Supplement converter data
• Add function table
• Log the new checksums
• Countersignature
Transfer of converter settings to
other identical machines by means
of series commissioning.
No.
Only check the control
of all of the safety func‐
tions.
• Add machine description
• Check checksums
• Check rmware versions
7.16 Safely Limited Speed (SLS)
Overview
4FMFDU4-4
4-4JTBDUJWF
63(('
/,0,7
Advanced commissioning
7.16Safely Limited Speed (SLS)
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 247