10.6.3 Downgrading the rmware
Introduction
When downgrading the rmware, you replace the converter rmware with an older version.
Only update the rmware to an older level if, after replacing a converter, you require the
same rmware in all converters.
Precondition
• Converter and memory card have dierent rmware versions.
• You have the memory card with the rmware for that particular converter.
• You have backed up the converter settings on the memory card or in a PC, or on the SINAMICS
G120 Smart Access.
Data backup and series commissioning (Page351)
Function description
The following procedure applies to both the G115D motor-mounted converter and the G115D
wall-mounted converter.
Procedure
1. Switch o the line voltage to the converter and (if installed) the external 24 V power supply
or the voltage for the digital outputs of the converter.
2. Wait until all LEDs on the converter are dark.
3. Insert the memory card with the matching rmware into the converter slot until it latches into
place.
4. Switch on the power supply of the converter again.
Corrective maintenance
10.6Firmware upgrade and downgrade