The reduced ux in the motor partial load range results in higher eciency.
Parameters
The converter calculates the parameters for the thermal motor model based on the motor data
that has been set – and the motor data identication.
Eciency optimization, method 2
Parameter Description Setting
p1401.14 Flux control conguration 1 signal: Eciency optimization 2 active
Factory setting: 0000 0000 0000 0110 bin
p1570[0...n] CO: Flux setpoint [%] Sets the ux setpoint referred to rated motor ux.
Factory setting: 100
p3315[0...n] Eciency optimization 2 minimum
ux limit value [%]
Sets the minimal limit value for the calculated op‐
timum ux.
Factory setting: 50
p3316[0...n] Eciency optimization 2 maxi‐
mum ux limit value [%]
Sets the maximum limit value for the calculated
optimum ux.
Factory setting: 110
Eciency optimization, method 1
Parameter Description Setting
p1570[0...n] CO: Flux setpoint [%] Sets the ux setpoint referred to rated motor ux.
Factory setting: 100
p1580[0...n] Eciency optimization [%] 0 %: Eciency optimization is deactivated.
100 %: In no-load operation, the converter reduces
the ux setpoint to 50% of the rated motor ux.
The factory setting depends on the converter.
7.29 Calculating the energy saving for uid ow machines
Overview
Fluid ow machines, which mechanically control the ow rate using valves or throttle aps,
operate with a constant speed corresponding to the line frequency.