Based on its thermal motor model, the converter continually determines - for the actual
operating point of the motor - the interdependency between e󹪟ciency and 󹪞ux. The
converter then sets the 󹪞ux to achieve the optimum e󹪟ciency.
)OX[
(IILFLHQF\
)OX[
(IILFLHQF\
(IILFLHQF\RSWLPL]DWLRQLVQRWDFWLYH
(IILFLHQF\RSWLPL]DWLRQLVDFWLYH




Depending on the motor operating point, the converter either decreases or increases the 󹪞ux
in partial load operation of the motor.
E󹪟ciency optimization, method 1
)OX[VHWSRLQW
7RUTXH1RORDGRSHUDWLRQ
5DWHGWRUTXH
3DUWLDOORDGRSHUDWLRQ
Sy
Sy
S
S 
S 
S 
The motor operates in partial load mode between no-load operation and the rated motor
torque. Depending on p1580, in the partial load range, the converter reduces the 󹪞ux
setpoint linearly with the torque.
Advanced commissioning
7.28E󹪟ciency optimization
SINAMICS G115D Wall Mounted distributed drive
336 Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA