6.3 Preparing for commissioning
6.3.1 Factory settings
Motor
For the SINAMICS G115D Wall Mounted drive, the converter is pre-congured for an
asynchronous motor that matches the rated power of the converter.
For the SINAMICS G115D Motor Mounted drive, the following converter settings have been
set in the factory to the delivery condition to match the provided 2KJ8 geared motor.
Parameter Description Delivery condition
p1300[0...n] Open-loop/closed-loop control op‐
erating mode
20: Speed control (encoderless)
p0300[0...n] Motor type selection The value is automatically preassigned to "181" or
"602" dependent upon the selected SINAMICS
G115D Motor Mounted drive.
181: 2KJ8 asynchronous motor
602: 2KJ8 synchronous reluctance motor
p0301[0...n] Motor code number selection The value is automatically preassigned dependent
upon the selected SINAMICS G115D Motor Moun‐
ted drive.
p0541[0...n] Load gearbox code number
p0551[0...n] Brake code number
p0601[0...n] Motor temperature sensor type
p1215 Motor holding brake conguration The value is automatically preassigned to "0" or "1"
dependent upon the selected SINAMICS G115D
Motor Mounted drive.
0: No motor holding brake available
1: Motor holding brake according to sequence con‐
trol
For more information about restoring settings to the delivery condition on the SINAMICS
G115D Motor Mounted drive, refer to the following section:
Restoring the factory settings/delivery condition (without safety functions) (Page126)
Converter interfaces
The inputs and outputs and the eldbus interface of the converter have specic functions when
set to the factory settings.
Factory interface setting (Page82)