Frame size Rated power Article number
FSC 5.5kW 6SL3500-0XE5 5 - 5 A0
7.5kW 6SL3500-0XE5 7 - 5 A0
AS-Interface A A0
I/O Control B A0
PROFINET, EtherNet/IP F A0
You can 󹪝nd the article number from the label on the back side of the Electronic Module.
Article number
10.3.2 Replacing the Electronic Module
WARNING
Electric shock as a result of a residual charge in power components
After the power supply has been switched o󹪜, it takes up to 5 minutes until the capacitors in the
converter have discharged so that the residual charge is at a non-hazardous level. Therefore,
touching the converter immediately after powering o󹪜 can result in electric shock due to
residual charge in the power components.
Check the voltage at the converter connections before you replace the Electronic Module.
Precondition
You have backed up the settings of the converter on an external storage medium.
Converter → Memory card (Page353)
Converter → PG/PC (Page358)
The new Electronic Module must have the same frame size and the same or higher power
rating as those of the Electronic Module that is necessary for replacement.
Procedure
1. Switch o󹪜 all power supplies (line supply and external 24 V power supply) to the converter.
2. Wait 5 minutes to allow the converter to discharge and check that no voltage is present at the
converter connections.
Corrective maintenance
10.3Replacing the spare parts
SINAMICS G115D Wall Mounted distributed drive
394 Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA