EasyManua.ls Logo

Siemens SINAMICS G115D

Siemens SINAMICS G115D
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The machine manufacturer decides whether or not a password is required.
The probabilities of failure (PFH) and certi󹪝cation of the safety functions also apply without
password.
What do I do if I lose the password?
You have forgotten the password, however, you would nevertheless like to change the
setting of the safety functions.
Procedure
1. Create a new project for the converter using Startdrive.
Leave all the factory setting in the project.
2. Load the project in the converter.
After loading, the converter has the factory settings.
3. Recommission the converter.
You can obtain more information or learn about alternative procedures from Technical
Support.
Parameters
Parameter Description Setting
p9761 SI password input Enters the Safety Integrated password.
0: No password set (factory setting)
1 ... FFFF FFFF: Password is set
p9762 SI password new Enters a new Safety Integrated password.
p9763 SI password acknowledgment Acknowledges the new Safety Integrated pass‐
word.
7.15.2.3 Con󹪝guring a safety function
Overview
To ensure protection against unauthorized changes, it is recommended that you con󹪝gure the
safety function settings.
Advanced commissioning
7.15Safe Torque O󹪜 (STO) safety function
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 237

Table of Contents

Related product manuals