Parameters Description Setting
p2182[0...n] Load monitoring speed threshold 1
[rpm]
Sets the speed/torque
envelope curve for load
monitoring.
• When using the con‐
trol mode "U/f con‐
trol" (p1300 < 10):
p2182 > 10% of the
rated speed
• When using the con‐
trol mode "encoder‐
less vector control"
(p1300 = 20):
p2182 > p1755
(switchover speed,
motor model)
Factory setting: 150
p2183[0...n] Load monitoring speed threshold 2
[rpm]
Factory setting: 900
p2184[0...n] Load monitoring speed threshold 3
[rpm]
Factory setting: 1500
p2186[0...n] Load monitoring torque threshold
1, lower [Nm]
Factory setting: 0
p2188[0...n] Load monitoring torque threshold
2, lower [Nm]
Factory setting: 0
p2190[0...n] Load monitoring torque threshold
3, lower [Nm]
Factory setting: 0
p2191[0...n] Load monitoring torque threshold,
no load [Nm]
Sets the torque threshold to identify dry running
operation for pumps or belt breakage for fans.
Factory setting: 0
p2192[0...n] Load monitoring delay time [s] Sets the delay time to evaluate the load monitoring.
Factory setting: 10
p2193[0...n] Load monitoring conguration Sets the load monitoring conguration:
1: Monitoring torque and load drop (factory set‐
ting)
4: Monitoring pump and load failure
5: Monitoring fan and load failure
Further information
If you deselect monitoring with p2193 < 4, the converter then resets the load monitoring
parameters to factory settings.