5. The converter transfers the rmware from the memory card into its memory.
The transfer takes approximately 5 to 10 minutes.
While data is being transferred, the LED RDY on the converter stays red. The BF or AS-i/FLT LED
ashes orange with a variable frequency.
%)RU$6L)/7
5'<
PLQ
9
6. At the end of the transfer, the LED RDY and BF (or AS-i/FLT) slowly ash red (0.5Hz).
Power supply failure during transfer
The converter rmware will be incomplete if the power supply fails during the transfer.
– Start again with step 1 of the instructions.
7. Switch o the power supply of the converter.
8. Wait until all LEDs on the converter are dark.
9. Remove the memory card from the converter.
Note: You can also leave the memory card in the converter. The converter will behave
dierently depending on whether the memory card contains a data backup:
– If the memory card contains a data backup of the converter settings:
⇒ The converter will take the settings from the memory card in step 10.
– If the memory card does not have a data backup of the converter settings:
⇒ The converter will reset to factory settings and write the settings to the memory card
in step 10.
Corrective maintenance
10.6Firmware upgrade and downgrade
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 407