5. Switch o the converter power supply.
6. Wait until all LEDs on the converter are dark.
7. Switch on the converter power supply again.
You have now congured the converter for communication via Ethernet/IP.
❒
Parameters
Parameter Description Setting
p2030 Fieldbus interface protocol selec‐
tion
0: No protocol
7: PROFINET
10: Ethernet/IP
The default setting is dependent upon the convert‐
er.
p8920 PN Name of Station Sets the station name for the onboard PROFINET
interface.
p8921 PN IP Address Sets the IP address for the onboard PROFINET inter‐
face.
Factory setting: 0
p8922 PN Default Gateway Sets the default gateway for the onboard PROFINET
interface.
Factory setting: 0
p8923 PN Subnet Mask Sets the subnet mask for the onboard PROFINET
interface.
Factory setting: 0
p8925 Activate PN interface conguration Setting to activate the interface conguration
0: No function (factory setting)
2: Activate and save conguration
3: Delete conguration
r8931 PN IP Address actual Displays the actual IP address.
r8932 PN Default Gateway actual Displays the actual default gateway.
r8933 PN Subnet Mask actual Displays the actual subnet mask.
p8980 Ethernet/IP prole Sets the prole for Ethernet/IP.
0: SINAMICS
1: ODVA AC/DC
p8981 Ethernet/IP ODVA STOP mode Sets the STOP mode for the Ethernet/IP ODVA pro‐
le (p8980 = 1).
0: OFF1 (factory setting)
1: OFF2
Advanced commissioning
7.6Drive control via Ethernet/IP
SINAMICS G115D Wall Mounted distributed drive
158 Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA