WARNING
Risk of electric shock and re from supply networks with an excessively low impedance
Excessively high short-circuit currents can lead to the protective devices not being able to
interrupt these short-circuit currents and being destroyed, and thus causing electric shock or a
re.
• Ensure that the prospective short-circuit current at the line terminal of the converter does
not exceed the breaking capacity (SCCR or Icc) of the protective device used.
WARNING
Electric shock if there is no ground connection
For missing or incorrectly implemented protective conductor connection for devices with
protection class I, high voltages can be present at open, exposed parts, which when touched,
can result in death or severe injury.
• Ground the device in compliance with the applicable regulations.
WARNING
Electric shock due to connection to an unsuitable power supply
When equipment is connected to an unsuitable power supply, exposed components may carry
a hazardous voltage. Contact with hazardous voltage can result in severe injury or death.
• Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV- (Protective
Extra Low Voltage) output voltages for all connections and terminals of the electronics
modules.
WARNING
Electric shock due to damaged motors or devices
Improper handling of motors or devices can damage them.
Hazardous voltages can be present at the enclosure or at exposed components on damaged
motors or devices.
• Ensure compliance with the limit values specied in the technical data during transport,
storage and operation.
• Do not use any damaged motors or devices.
WARNING
Electric shock due to unconnected cable shield
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
• Attach the cable shields at least on one side to the grounded housing potential.
Fundamental safety instructions
2.1General safety instructions
SINAMICS G115D Wall Mounted distributed drive
18 Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA