Parameters
Parameters of the alarm buer and the alarm history
Parameter Description Setting
p2111 Alarm counter Number of alarms that have occurred after the last
reset.
When setting p2111 = 0, the following is initiated:
• All of the alarms that have been removed from
the alarm buer [0...7] are transferred into the
alarm history [8...63].
• The alarm buer [0...7] is deleted.
Factory setting: 0
r2122[0…63] Alarm code Displays the numbers of the alarms that have oc‐
curred.
r2123[0…63] Alarm time received in milli‐
seconds
Displays the time in milliseconds when the alarm
occurred.
r2124[0…63] Alarm value Displays additional information about the alarm.
r2125[0…63] Alarm time removed in milli‐
seconds
Displays the time in milliseconds when the alarm
was removed.
r2132 CO: Actual alarm code Displays the code of the alarm that last occurred.
r2134[0…63] Alarm value for oat values Displays additional information about the alarm
that occurred for oat values.
r2145[0…63] Alarm time received in days Displays the time in days when the alarm occurred.
r2146[0…63] Alarm time removed in days Displays the time in days when the alarm was re‐
moved.
Extended settings for alarms
Parameter Description Setting
You can change up to 20 dierent alarms into faults or suppress alarms:
p2118[0…19] Changing message type, mes‐
sage number
Selects faults or alarms for which the message type
should be changed.
Factory setting: 0
p2119[0…19] Changing message type, type Sets the message type for the selected fault or
alarm.
1: Fault
2: Alarm
3: No message
Factory setting: 1
For more information about this function, see function diagram 8075 and parameter
description in the List Manual.
Alarms, faults and system messages
9.4Alarms, alarm buer, and alarm history
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 377