EasyManua.ls Logo

Siemens SINAMICS G115D - Corrective maintenance; 10.1 Spare parts compatibility

Siemens SINAMICS G115D
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Number Cause Remedy
A07981 No enabling for rotary measurement Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
A07991 Motor data identi󹪝cation activated Switch on the motor and identify the motor data.
F08501 Setpoint timeout
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the set monitoring time p2044.
F08502 Monitoring time sign-of-life expired
Check the PROFINET connection.
A08511 Receive con󹪝guration data not valid
Check the PROFINET con󹪝guration
A08526 No cyclic connection
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565 Consistency error a󹪜ecting adjusta‐
ble parameters
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
F13100 Know-how protection: Copy protec‐
tion error
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily o󹪜 and then on again (POWER ON).
Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy protec‐
tion cannot be activated
Insert a valid memory card.
F30001 Overcurrent Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
U/f operation: Assignment of rated currents of motor and Power Module
Line quality
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
U/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
F30002 DC-link voltage overvoltage Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
F30003 DC-link voltage undervoltage Check the line voltage (p0210).
Alarms, faults and system messages
9.6List of alarms and faults
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 385

Table of Contents

Related product manuals